Amana Air Conditioner Error Codes
Amana Air Conditioner Maintenance Dubai
Amana Air Conditioner Error Codes
Standard and Remote Applications with LED M70 Control Board and R-410A
MODES
CODE: FP
STATUS: Freeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F.
SUGGESTED ACTION: No Action required. This setting will disengage when the room temperature rises above 43°F.
CODE: Fd
STATUS: Front Desk switch is closed. All outputs are switched off.
SUGGESTED ACTION: Open front desk switch to allow occupant unit operation.
CODE: Eo
STATUS: Un-Configured Service Board – All operation held awaiting configuration
SUGGESTED ACTION: Enter Configuration Menu and set “C3” to “C” for coolers with electric heat or “H” for heat pumps.
CODE: EH
STATUS: Emergency Hydronic Engaged. The EHH switch is closed. Compressor is switched off.
SUGGESTED ACTION: Open front emergency hydronic switch to allow occupant unit operation.
CODE: LS
STATUS: Load Shedding Engaged. The LS switch is closed. Compressor and Electric heat is switched off.
SUGGESTED ACTION: Open load shedding switch to allow occupant unit operation.
CODE: On
STATUS: Control is configured to respond to a wired thermostat
SUGGESTED ACTION: No action if a wired thermostat is being used.
CODE: oP
STATUS: Open Door Lockout (DS1 & DS2 open; wireless)
SUGGESTED ACTION: Close Room Door. Unit will not condition space with door open.
CODE: nP
STATUS: Window Switch Lockout – (LS & INN open)
SUGGESTED ACTION: Close Room Door or Window. Unit will not condition space with door or window open.
CODE: HP
STATUS: Heat Sentinel – (WIAT > u3)
SUGGESTED ACTION: No action required. This setting will disengage when the room temperature falls.
CODE: Ur
STATUS: Un-Rented Status (EHH & INN or wireless)
SUGGESTED ACTION: Front Desk needs to set to Rented mode (if applicable)
FAILURES
CODE: F1
STATUS:
- Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control or
- Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F.
SUGGESTED ACTION: Replace black Indoor Ambient Thermistor or Wireless Remote Thermostat.
CODE: F2
STATUS: Wireless Remote Thermostat failure
SUGGESTED ACTION: Replace Wireless Thermostat.
CODE: F3
STATUS: Indoor Ambient Thermistor reads outside the range -20°F to 200°F
SUGGESTED ACTION: Replace black Indoor Ambient Thermistor.
CODE: F4
STATUS: Indoor Coil Thermistor either above or below operating tolerances.
SUGGESTED ACTION: Replace Red Indoor Coil Thermistor .
CODE: F5
STATUS: Wireless Thermostat failure
SUGGESTED ACTION: Attempt to rebind Wireless Thermostat or Replace Wireless Thermostat.
CODE: F6
STATUS: Indoor Discharge Thermistor either above or below operating tolerances.
SUGGESTED ACTION: Replace Yellow Indoor Discharge Thermistor.
CODE: Fb
STATUS: Low Remote Battery Warning.
SUGGESTED ACTION: Replace Batteries in Wireless Devices.
CODE: H1
STATUS: High Voltage Protection engaged. Power supply voltage is to high.
SUGGESTED ACTION: Check for incoming power at correct voltage.
CODE: br
STATUS: Brown Out Protection engaged. Power was lost or voltage is low
SUGGESTED ACTION: Check for incoming power at correct voltage.
AIRFLOW ALERTS
CODE: L6
STATUS: Discharge Air Too Hot.
SUGGESTED ACTION: Clean Filter or Remove Air Blockage.
CODE: LC
STATUS: Outdoor Coil Thermistor temperature high.
SUGGESTED ACTION: Clean Condenser Coils, Check Fan for fault. Code will reset after cleaning
CODE: C2
STATUS: Indoor Air Recirculation. Large delta between thermostat and return.
SUGGESTED ACTION: Clean Filter or Remove Air Blockage or Close Vent Door or Improve indoor to outdoor seal.
CODE: C5
STATUS: Outdoor Coil temperature too high for outdoor ambient temperature.
SUGGESTED ACTION: Check for Blocked Outdoor Air or Clean Coil.
REFRIGERATION ALERTS
CODE: C1
STATUS: Indoor Coil is freezing up
SUGGESTED ACTION: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.
CODE: C3
STATUS: Indoor Coil is freezing up.
SUGGESTED ACTION: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.
CODE: C4
STATUS: Indoor Coil froze up.
SUGGESTED ACTION: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.
CODE: C6
STATUS: Poor Unit Performance.
SUGGESTED ACTION: Check for blower motor, compressor, or electric heat operation.
CODE: C7
STATUS: Indoor Freezing Lockout (ICT – IAT > 20) +10 Min
SUGGESTED ACTION: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.