Posts

Bryant Air Conditioners Error Codes

Bryant Air Conditioners Error Codes

Bryant Ac Maintenance Dubai

Table 19 shows the status codes flashed by the amber status light.Most system problems can be diagnosed by reading the status code as flashed by the amber status light on the control board.

The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code.

Bryant Air Conditioners Error Codes

A NOTE ABOUT SAFETY Any time you see this symbol in manuals, instructions and on the unit, be aware of the potential for personal injury. There are three levels of precaution: DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

PERSONAL INJURY, DEATH AND / OR PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury, death or property damage. Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or service agency must use factory–authorized kits or accessories when modifying this product. Read and follow all instructions and warnings, including labels shipped with or attached to unit before operating your new air conditioner.

ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Disconnect all electrical power to the indoor air handler or furnace before removing access panels to perform any maintenance. Disconnect power to both the indoor and outdoor units.

Bryant Air Conditioners Heat Pumps Troubleshooting Dubai

Fault: System Communications Failure

Possible Cause And Action: Communication with User Interface lost. Check wiring to User Interface, indoor and outdoor units

Fault: Invalid Model Plug

Possible Cause And Action: Control does not detect a model plug or detects an invalid model plug. Unit will not operate without correct model plug

Fault: High Pressure Switch Open

Possible Cause And Action: High —pressure switch trip. Check refrigerant charge, outdoor fan operation and coils for airflow restrictions

Fault: Low Pressure Switch or Discharge Temp Switch Open

Possible Cause And Action: Low -pressure switch or discharge temperature switch trip. Check refrigerant charge and indoor air flow.

Fault: Control Fault

Possible Cause And Action: Outdoor unit control board has failed. Control board needs to be replaced.

Fault: Outdoor Air Temp Sensor Fault

Possible Cause And Action: Outdoor air sensor not reading or out of range. Ohm out sensor and check wiring

Fault: Outdoor Coil Sensor Fault

Possible Cause And Action: Coil sensor not reading or out of range. Ohm out sensor and check wiring

Fault: Thermistors out of range

Possible Cause And Action: Improper relationship between coil sensor and outdoor air sensor. Ohm out sensors and check wiring

Fault: Low Stage Thermal Cutout

Possible Cause And Action: Compressor operation detected then disappears while low stage demand exists. Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long

Fault: High Stage Thermal Cutout

Possible Cause And Action: Compressor operation detected then disappears while high stage demand exists. Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long

Fault: Low Stage Thermal Lockout

Possible Cause And Action: Thermal cutout occurs in three consecutive low/high stage cycles. Low stage locked out for 4 hours or until 24v power recycled.

Contact us

Beko AC Error Codes and Troubleshooting

Beko Ac Error Codes and Trouble Shooting

Beko Ac Maintenance Dubai

When air conditioner status is abnormal, temperature indicator on indoor unit will blink to display corresponding error code. Please refer to blow list for identification of error.

Error Codes Cause
H1 Means defrosting status. It’s the normal phenomenon.
E5 It can be eliminated after restarting the unit. If not, please contact qualified professionals for service.
U8 It can be eliminated after restarting the unit. If not, please contact qualified professionals for service.
H6 It can be eliminated after restarting the unit. If not, please contact qualified professionals for service.
C5 Please contact qualified professionals for service.
F1 Please contact qualified professionals for service.
F2 Please contact qualified professionals for service.

Note: If there’re other error codes, please contact qualified professionals for service.

Warning

When below phenomenon occurs, please turn off air conditioner and disconnect power immediately, and then contact the dealer or qualified professionals for service.

  • Power cord is overheating or damaged.
  • There’s abnormal sound during operation.
  • Circuit break trips off frequently.
  • Air conditioner gives off burning smeel.
  • Indoor unite is leaking.

*Do not repair or refit the air conditioner by yourself.
*If the air conditioner operates under abnormal conditions, it may cause malfunction, electric shock or fire hazard.

Beko AC Troubleshooting

Check the following points before requesting repairs or service. If the fault persists, please contact your dealer or service center.

*The air conditioner does no operate.
-Have you made a mistake in timer operation?
-Has the fuse blown or has the circuit breaker been tripped?

*The room has a peculiar odor.
-Check that this is not a damp smell exuded by the walls, carpet, furniture, or cloth items in the room.

*It seems that condensation is leaking from the air conditioner.
-Condensation occurs when the airflow from the air conditioner cools the warm room air.

*Air conditioner does not operate for about 3 minutes when restarted.
-This is the protector of the mechanism.
-Wait about three minutes and operation will begin.

*Does not cool or heat effectively.
– Is the air filter dirty? See air filter cleaning instructions.
– Has the temperature been set incorrectly?
– Are the indoor unit’s air inlet or outlet vents obstructed?

*The air conditioner operation is noisy.
-For a noise that sounds like water flowing. This is the sound of freon flowing inside the air conditioner unit.
-For a noise that sounds like the compressed air releasing into atmosphere. This is the sound of the dehumidifying water being processed inside the air conditioning unit.

*Remote control display is faint, or no display at all.
-Are the batteries depleted?
-Are the batteries inserted in the opposite (+) and (-) directions?

*Crack sound is heard.
This sound is generated by the expansion/constriction of the front panel, etc. due to changes of temperature.

Contact us

Aux AC Error Codes and Troubleshooting

Aux Ac Error Codes and Trouble Shooting

Aux Ac Maintenance Dubai

AUX Air Conditioning Error Codes;

1.HS(Y) HSA(Y) HSB(Y) HSF (Y) HV(Y) HVA(Y) digital display for the series air-conditioner faults:

Error Codes Problem
E4 PG motor feedback is abnormal. The display precedence level: 1
E1 Plastic temp sensor is abnormal. The display precedence level: 2
E3 Copper temp sensor is abnormal (indoor). The display precedence level: 3
E2 Copper temp sensor is abnormal (outdoor). The display precedence level: 4

2. H (Except KFR-25G/H) H1 HA HB series faults display:

  • Fault source: PG motor feedback is abnormal
  • Display mode: Timing light twinkles 4 times in every 8 seconds
  • The display precedence level: 1
  • Fault source: Plastic temp sensor is abnormal
  • Display mode: Timing light twinkles 1 times in every 8 seconds
  • The display precedence level: 2
  • Fault source: Copper temp sensor is abnormal (indoor)
  • Display mode: Timing light twinkles 2 times in every 8 seconds
  • The display precedence level: 3
  • Fault source: Copper temp sensor is abnormal (indoor)
  • Display mode: Timing light twinkles 1 times in every 1 seconds
  • The display precedence level: 4

3. H(Y) Model air conditioner fault display:

  • Fault source: PG motor feedback is abnormal
  • Display mode: Timing light twinkles 4 times in every 8 seconds
  • The display precedence level: 1
  • Fault source: Plastic temp sensor is abnormal
  • Display mode: Timing light twinkles 1 times in every 8 seconds
  • The display precedence level: 2
  • Fault source: Copper temp sensor is abnormal (indoor)
  • Display mode: Timing light twinkles 2 times in every 8 seconds
  • The display precedence level: 3
  • Fault source: Copper temp sensor is abnormal (outdoor)
  • Display mode: Timing light twinkles 1 times in every 1 seconds
  • The display precedence level: 4

4. EA EC EM EY EZ EAA EAD EL HS1 HSZ HL1 HLZ P P1 ZZ CZ digital display series ac faults:

  • Fault source: PG motor feedback is abnormal
  • Display mode: E4
  • The display precedence level: 1
  • Fault source: Plastic temp sensor is abnormal
  • Display mode: E1
  • The display precedence level: 2
  • Fault source: Copper temp sensor is abnormal (indoor)
  • Display mode: E3
  • The display precedence level: 3

5. All of the other E series except EA EC EM EY EZ EAA EAD:

  • Fault source: PG motor feedback is abnormal
  • Display mode: Timing light twinkles 4 times in every 8 seconds
  • The display precedence level: 1
  • Fault source: Plastic temp sensor is abnormal
  • Display mode: Timing light twinkles 1 times in every 8 seconds
  • The display precedence level: 2
  • Fault source: Copper temp sensor is abnormal (indoor)
  • Display mode: Timing light twinkles 2 times in every 8 seconds
  • The display precedence level: 3

6. QA QB QD digital display series ac faults:

  • Fault source: PG motor feedback is abnormal
  • Display mode: E4
  • The display precedence level: 1
  • Fault source: Plastic temp sensor is abnormal
  • Display mode: E1
  • The display precedence level: 2
  • Fault source: Copper temp sensor is abnormal
  • Display mode: E3
  • The display precedence level: 3
  • Fault source: Over-current oprotection
  • Display mode: E6
  • The display precedence level: 4

7. QC QQ light display series air-conditioner faults:

  • Fault source: PG motor feedback is abnormal
  • Display mode: Timing light twinkles 4 times in every 8 seconds
  • The display precedence level: 1
  • Fault source: Plastic temp sensor is abnormal
  • Display mode: Timing light twinkles 1 times in every 8 seconds
  • The display precedence level: 2
  • Fault source: Copper temp sensor is abnormal
  • Display mode: Timing light twinkles 3 times in every 8 seconds
  • The display precedence level: 3
  • Fault source: Over-current oprotection
  • Display mode: Timing light twinkles 6 times in every 8 seconds
  • The display precedence level: 4

8. Faults display of 18000BTU~24000BTU wall unit series ac non-digital tube displays:

  • Fault source: PG motor feedback is abnormal
  • Display mode: Timing light twinkles 1 times in every 8 seconds
  • The display precedence level: 2
  • appearance: System turns off
  • Fault source: Plastic temp sensor is abnormal
  • Display mode: Timing light twinkles 2 times in every 8 seconds
  • The display precedence level: 3
  • appearance: System turns off
  • Fault source: Copper temp sensor is abnormal
  • Display mode: Timing light twinkles 8 times in every 8 seconds
  • The display precedence level: 4
  • appearance: System doesn’t turns off

Digital tube displays:

  • Fault source: PG motor feedback is abnormal
  • Display mode: E1
  • The display precedence level: 2
  • appearance: System turns off
  • Fault source: Plastic temp sensor is abnormal
  • Display mode: E3
  • The display precedence level: 3
  • appearance: System turns off
  • Fault source: Copper temp sensor is abnormal
  • Display mode: E2
  • The display precedence level: 4
  • appearance: System doesn’t turn off
  • E1: Temperature sensor of air intake fault
  • E2: Temperature sensor of outdoor coil fault
  • E3: Temperature sensor of indoor coil fault
  • E4: PG motor of indoor unit feedback fault

AUX Air Conditioning Wall Mounted Error Codes

Self-check information: Hint to defrosting

  • Self-check code of luminotron: Flicker 1 time/1s
  • Digital self-check code: Indicates “dF“or defrosting indicator displays

Self-check information: Hint to defense against cold wind

  • Self-check code of luminotron: Flicker 1 time/3s
  • Digital self-check code: Fan motor picture not running

Self-check information: Failure of room temperature sensor

  • Self-check code of luminotron: Flicker 2 times/4s (Flicker 2 times/8s)
  • Digital self-check code: E2/(L2)

Self-check information: Failure of coiled pipe sensor

  • Self-check code of luminotron: Flicker 3 times/5s (Flicker 1 time/8s)
  • Digital self-check code: E3/(L1)

Self-check information: Abnormality of outdoor unit

  • Self-check code of luminotron: Flicker 4 times/6s (luminating)
  • Digital self-check code: E4/(E5)

Self-check information: Without feedback of internal fan motor

  • Self-check code of luminotron: Flicker 5 times/7s (Flicker 6 times/8s)
  • Digital self-check code: E5/(L6)

Self-check information: Zero crossing signal without current

  • Self-check code of luminotron: Flicker 6 times/8s
  • Digital self-check code: E6

Self-check information: External feedback failure

  • Self-check code of luminotron: Flicker 7 times/9s
  • Digital self-check code: E7

Self-check information: Overheat protection

  • Self-check code of luminotron: Flicker 8 times/10s
  • Digital self-check code: E8

Self-check information: Water pump failure

  • Self-check code of luminotron: Flicker 9 times/11s
  • Digital self-check code: E9

Troubleshooting Guide

Problem: The motor is heard operating but the air-conditioner dose not work when the indoor unit is powered on

Cause: Since the air-conditioner is powered on, it will come to working condition as long as you press the ON/OFF button of the remote control and the signal is well received.

Problem: The compressor stops running but the indoor fan motor keeps working when it is at cooling mode with the indoor temperature higher than set temperature.

Cause: If you turn off the air-conditioner and restart it immediately, it will return to normal in 3 minutes, after that, the air-conditioner will automatically adjust the indoor fan speed to what you set.

Problem: The compressor works discontinuously at dehumidifying mode.

Cause: The air-conditioner will automatically control the working of the compressor according to the inside temperature

Problem: The air-conditioner dose not work while the LED display is on.

Cause: The TIMER is set with the air-conditioner,it will be in hold on condition. If the TIMER setting is cancelled, the air-conditioner will return to normal working condition.

Problem: The compressor works discontinuously at cooling and dehumidifying mode, and the indoor fan motor slows down.

Cause: The compressor stops internally or the fan motor slows down to prevent the indoor heat exchanger from being frozen.

Contact us

Amvent Air Conditioner Error Codes

Amvent Air Conditioner Error Codes

Amvent Ac Maintenance Dubai

Amvent Mini Split AC; In case of error, the display on the indoor unit shown the following error codes:

E1-flashes once -The fault of indoor temperature senser

E2-flashes twice-The fault of indoor pipe temperature senser

E6-flashes 6 times-Malfunction of indoor fan motor

Troubleshooting

Malfunction: The Air Conditioner does not operate

Possible Causes:

  • Ac Power failure/plug pulled out
  • Ac Damaged indoor/outdoor unit Ac fan motor
  • Faulty compressor thermomagnetic circuit breaker
  • Faulty protective device or fuses.
  • Loose connections or plug pulled out
  • It sometimes stops operating to protect the appliance.
  • Voltage higher or lower than the voltage range
  • Active TIMER-ON function
  • Damaged electronic control board (PCB)

Malfunction: Strange odour

Possible Causes: Dirty Ac air filter

Malfunction: Noise of running water

Possible Causes: Back flow of liquid in the refrigerant circulation

Malfunction: A fine mist comes from the air outlet

Possible Causes: This occurs when the air in the room becomes very cold, for example in the COOLING or DEHUMIDIFYING/DRY modes

Malfunction: A strange noise can be heard

Possible Causes: This noise is made by the expansion or contraction of the front panel due to variations in temperature and does not indicate a problem.

Malfunction: Insufficient airflow, either hot or cold

Possible Causes:

  • Unsuitable temperature setting.
  • Obstructed air conditioner intakes and outlets.
  • Dirty air filter.
  • Fan speed set at minimum.
  • Other sources of heat in the room.
  • No refrigerant.

Malfunction: The appliance does not respond to commands

Possible Causes:

  • Remote control is not near enough to indoor unit.
  • The batteries of remote control nearly has no power.
  • Obstacles between remote control and signal receiver in indoor unit.

Malfunction: The display is off

Possible Causes:

  • Active LIGHT function
  • Power failure

Malfunction: Switch off the air condi- tioner immediately and cut off the power supply in the event of

Possible Causes:

  • Strange noises during operation.
  • Faulty electronic control board
  • Faulty fuses or switches.
  • Spraying water or objects inside the appliance.
  • Overheated cables or plugs.
  • Very strong smells coming from the appliance.

Contact us

Amana PTAC AC Error Codes

Amana Air Conditioner Maintenance Dubai

Package Terminal, Air Conditioner/Heat Pump. Amana Diagnostic Codes;

MODES:

Error Code: FP

  • Status: Freeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F
  • Suggested Action: No Action required. This setting will disengage when the room temperature rises above 43°F.
  • Display: Y
  • Error Light: N

Error Code: Fd

  • Status: Front Desk switch is closed. All outputs are switched off
  • Suggested Action: Open front desk switch to allow occupant unit operation
  • Display: Y
  • Error Light: N

Error Code: Eo  

  • Status: Un-Configured Service Board – All operation held awaiting configuration
  • Suggested Action: Enter Configuration Menu and set “C3” to “C” for coolers with electric heat or “H” for heat pumps.
  • Display: Y
  • Error Light: Y

Error Code: EH

  • Status: Emergency Hydronic Engaged. The EHH switch is closed. Compressor is switched off.
  • Suggested Action: Open front emergency hydronic switch to allow occupant unit operation.
  • Display: Y
  • Error Light: N

Error Code: LS 

  • Status: Load Shedding Engaged. The LS switch is closed. Compressor and Electric heat is switched off
  • Suggested Action: Open load shedding switch to allow occupant unit operation
  • Display: Y
  • Error Light: N

Error Code: On  

  • Status: Control is configured to respond to a wired thermostat
  • Suggested Action: No action if a wired thermostat is being used. Otherwise, see Configuration Settings.
  • Display: Y
  • Error Light: N

Error Code: oP 

  • Status: Open Door Lockout (DS1 & DS2 open; wireless)
  • Suggested Action: Close Room Door. Unit will not condition space with door open.
  • Display: Y
  • Error Light: Y

Error Code: nP 

  • Status: Window Switch Lockout – (LS & INN open)
  • Suggested Action: Close Room Door or Window. Unit will not condition space with door or window open
  • Display: Y
  • Error Light: Y

Error Code: HP  

  • Status: Heat Sentinel – (WIAT > u3)
  • Suggested Action: No action required. This setting will disengage when the room temperature falls
  • Display: Y
  • Error Light: N

Error Code: Ur 

  • Status: Un-Rented Status (EHH & INN or wireless)
  • Suggested Action: Front Desk needs to set to Rented mode (if applicable)
  • Display: Y
  • Error Light: N

FAILURES;

Error Code: F1

  • Status: Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control or Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F
  • Suggested Action: Replace black Indoor Ambient Thermistor or Wireless Remote Thermostat
  • Display: Y
  • Error Light: Y

Error Code: F2

  • Status: Wireless Remote Thermostat failure
  • Suggested Action: Replace Wireless Thermostat
  • Display: N
  • Error Light: N

Error Code: F3 

  • Status: Indoor Ambient Thermistor reads outside the range -20°F to 200°F
  • Suggested Action: Replace black Indoor Ambient Thermistor
  • Display: Y
  • Error Light: N

Error Code: F4 

  • Status: Indoor Coil Thermistor either above or below operating tolerances
  • Suggested Action: Replace Red Indoor Coil Thermistor
  • Display: N
  • Error Light: Y

Error Code: F5  

  • Status: Wireless Thermostat failure
  • Suggested Action: Attempt to rebind Wireless Thermostat or Replace Wireless Thermostat
  • Display: N
  • Error Light: Y

Error Code: F6 

  • Status: Indoor Discharge Thermistor either above or below operating tolerances
  • Suggested Action: Replace Yellow Indoor Discharge Thermistor
  • Display: N
  • Error Light: Y

Error Code: Fb 

  • Status: Low Remote Battery Warning
  • Suggested Action: Replace Batteries in Wireless Devices
  • Display: N
  • Error Light: Y

Error Code: H1 

  • Status: High Voltage Protection engaged. Power supply voltage is to high
  • Suggested Action: Check for incoming power at correct voltage
  • Display: Y
  • Error Light: N

Error Code: br

  • Status: Brown Out Protection engaged. Power was lost or voltage is low
  • Suggested Action: Check for incoming power at correct voltage
  • Display: N
  • Error Light: N

AIRFLOW ALERTS;

Error Code: L6   

  • Status: Discharge Air Too Hot
  • Suggested Action: Clean Filter or Remove Air Blockage
  • Display: N
  • Error Light: Y

Error Code: LC  

  • Status: Outdoor Coil Thermistor temperature high
  • Suggested Action: Clean Condenser Coils, Check Fan for fault. Code will reset after cleaning
  • Display: N
  • Error Light: Y

Error Code: C2 

  • Status: Indoor Air Recirculation. Large delta between thermostat and return
  • Suggested Action: Clean Filter or Remove Air Blockage or Close Vent Door or Improve indoor to outdoor seal.
  • Display: N
  • Error Light: Y

Error Code: C5 

  • Status: Outdoor Coil temperature too high for outdoor ambient temperature
  • Suggested Action: Check for Blocked Outdoor Air or Clean Coil
  • Display: N
  • Error Light: Y

REFRIGERATION ALERTS;

Error Code: C1 

  • Status: Indoor Coil is freezing up
  • Suggested Action: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tub
  • Display: N
  • Error Light: Y

Error Code: C3

  • Status: Indoor Coil is freezing up
  • Suggested Action: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube
  • Display: N
  • Error Light: Y

Error Code: C4 

  • Status: Indoor Coil froze up
  • Suggested Action: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube
  • Display: N
  • Error Light: Y

Error Code: C6 

  • Status: Poor Unit Performance
  • Suggested Action: Check for blower motor, compressor, or electric heat operation
  • Display: N
  • Error Light: Y

Error Code: C7 

  • Status: Indoor Freezing Lockout (ICT – IAT > 20) +10 Min
  • Suggested Action: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube
  • Display: N
  • Error Light: Y

Contact us

Amana Air Conditioner Error Codes

Amana Air Conditioner Maintenance Dubai

Amana Air Conditioner Error Codes

Standard and Remote Applications with LED M70 Control Board and R-410A

MODES

CODE: FP

STATUS: Freeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F.

SUGGESTED ACTION: No Action required. This setting will disengage when the room temperature rises above  43°F.


CODE: Fd

STATUS: Front Desk switch is closed. All outputs are switched off.

SUGGESTED ACTION: Open front desk switch to allow occupant unit operation.


CODE: Eo

STATUS: Un-Configured Service Board – All operation held awaiting configuration

SUGGESTED ACTION: Enter Configuration Menu and set “C3” to “C” for coolers with electric heat or “H” for heat pumps.


CODE: EH

STATUS: Emergency Hydronic Engaged. The EHH switch is closed. Compressor is switched off.

SUGGESTED ACTION: Open front emergency hydronic switch to allow occupant unit operation.


CODE: LS

STATUS: Load Shedding Engaged. The LS switch is closed. Compressor and Electric heat is switched off.

SUGGESTED ACTION: Open load shedding switch to allow occupant unit operation.


CODE: On

STATUS: Control is configured to respond to a wired thermostat

SUGGESTED ACTION: No action if a wired thermostat is being used.


CODE: oP

STATUS: Open Door Lockout (DS1 & DS2 open; wireless)

SUGGESTED ACTION: Close Room Door. Unit will not condition space with door open.


CODE: nP

STATUS: Window Switch Lockout – (LS & INN open)

SUGGESTED ACTION: Close Room Door or Window. Unit will not condition space with door or window open.


CODE: HP

STATUS: Heat Sentinel – (WIAT > u3)

SUGGESTED ACTION: No action required. This setting will disengage when the room temperature falls.


CODE: Ur

STATUS: Un-Rented Status (EHH & INN or wireless)

SUGGESTED ACTION: Front Desk needs to set to Rented mode (if applicable)


FAILURES

CODE: F1

STATUS:

  • Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control or
  • Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F.

SUGGESTED ACTION: Replace black Indoor Ambient Thermistor or Wireless Remote Thermostat.


CODE: F2

STATUS: Wireless Remote Thermostat failure

SUGGESTED ACTION:  Replace Wireless Thermostat.


CODE: F3

STATUS: Indoor Ambient Thermistor reads outside the range -20°F to 200°F

SUGGESTED ACTION: Replace black Indoor Ambient Thermistor.


CODE: F4

STATUS: Indoor Coil Thermistor either above or below operating tolerances.

SUGGESTED ACTION: Replace Red Indoor Coil Thermistor .


CODE: F5

STATUS: Wireless Thermostat failure

SUGGESTED ACTION: Attempt to rebind Wireless Thermostat or Replace Wireless Thermostat.


CODE: F6

STATUS: Indoor Discharge Thermistor either above or below operating tolerances.

SUGGESTED ACTION: Replace Yellow Indoor Discharge Thermistor.


CODE: Fb  

STATUS: Low Remote Battery Warning.

SUGGESTED ACTION: Replace Batteries in Wireless Devices.


CODE: H1

STATUS: High Voltage Protection engaged. Power supply voltage is to high.

SUGGESTED ACTION: Check for incoming power at correct voltage.


CODE: br 

STATUS: Brown Out Protection engaged. Power was lost or voltage is low

SUGGESTED ACTION: Check for incoming power at correct voltage.

AIRFLOW ALERTS

CODE: L6

STATUS: Discharge Air Too Hot.

SUGGESTED ACTION:  Clean Filter or Remove Air Blockage.


CODE: LC

STATUS: Outdoor Coil Thermistor temperature high.

SUGGESTED ACTION: Clean Condenser Coils, Check Fan for fault. Code will reset after cleaning


CODE: C2  

STATUS: Indoor Air Recirculation. Large delta between thermostat and return.

SUGGESTED ACTION: Clean Filter or Remove Air Blockage or Close Vent Door or Improve indoor to outdoor seal.


CODE: C5 

STATUS: Outdoor Coil temperature too high for outdoor ambient temperature.

SUGGESTED ACTION: Check for Blocked Outdoor Air or Clean Coil.

REFRIGERATION ALERTS

CODE: C1 

STATUS: Indoor Coil is freezing up

SUGGESTED ACTION: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.


CODE: C3 

STATUS: Indoor Coil is freezing up.

SUGGESTED ACTION: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.


CODE: C4 

STATUS: Indoor Coil froze up.

SUGGESTED ACTION: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.


CODE: C6 

STATUS: Poor Unit Performance.

SUGGESTED ACTION: Check for blower motor, compressor, or electric heat operation.


CODE: C7

STATUS: Indoor Freezing Lockout (ICT – IAT > 20) +10 Min

SUGGESTED ACTION: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

Contact us

Amana Through the Wall (TTW) AC Error Codes and Troubleshooting

Amana Ac Maintenance Dubai

Amana Air Conditioner Normal Operating Sounds And Conditions:

Popping Or Gurgling Sounds: This sound is the refrigerant traveling through the lines. This is a normal sound which may be heard for a few seconds after the unit shuts off.

Water Trickling Sounds: This sound is produced by the water as it is picked up and run over the coils. This procedure improves the efficiency of the unit and helps with water removal.

Water Dripping: Water will collect in the base pan during high humidity days.

Starting Delay: You may notice a short delay in the startup if you try to restart the unit too soon after turning it off or if you adjust the thermostat right after the compressor has shut off. This delay protects the compressor.


Error Code: F1

Status: Outdoor ambient thermostat not registering on the board.

Corrective Action: Replace or re-connect the thermostat.


Error Code: F2

Status: Outdoor ambient thermostat not registering on the board.

Corrective Action: Replace or re-connect the thermostat.


Error Code: F4

Status: Outdoor coil thermostat not rgistering on the board.

Corrective Action: Replace or re-connect the thermostat.


Error Code: FJ

Status: Indoor discharge thermostat not registering on the board.

Corrective Action: Replace or re-connect the thermostat.


Additional Information

  • The remote control will operate all the control panel features. Instructions will be the same.
  • The “COOL” circuit has an automatic 3 minute time delayed start if the unit is turned off and on quickly. This prevents overheating of the compressor and possible circuit breaker tripping. NOTE: The fan will continue to run during this time.
  • The control will maintain any set temperature between 60°F and 90°F (cooling), 55°F and 80°F (heating).
  • The control is capable of displaying temperature in degrees (Fahrenheit) or degrees (Celsius). To convert from one to the other, press and hold the UP and DOWN Temperature Selection Pads at the same time for 3 seconds.

Compressor

The compressor is hermetically sealed, permanently lubricated and requires no additional oiling.

Front Panel And Grille

The front panel and grille can be cleaned with a mild soap or detergent. Do not use hydrocarbon-based cleaners (e.g. acetone, benzene, naphtha, gasoline, etc.) to clean the front panel or grille. Use care when cleaning the control area. Do not use an excessively wet cleaning cloth.

Scheduled Ac Maintenance

To achieve continuing top performance and high efficiency, a regular cleaning/inspection schedule must be established. Maintaining this schedule can be accomplished by either a local maintenance staff or an authorized service and must follow the instructions described in this manual.

  • If the unit is operated in a dusty climate, dust may collect in the base pan and clog the condenser coil. It is advisable to remove the unit from the sleeve and thoroughly clean the base pan and condenser coil on a periodic basis.
  • If the unit is installed ocean side or in a corrosive atmosphere, its life may be greatly reduced by the corrosive environment. Under these conditions, the unit should be removed from the sleeve and completely cleaned once a year. At that time any scratches or blisters on the painted surfaces should be sanded and repainted.

Air Conditioner Outdoor Coil Cleaning

The coils on the outdoor side of the air conditioner should be checked regularly. For cleaning outside coil, remove the 6 screws that mount the condenser coil top cover to condenser shroud.

Contact us

Alliance Air Conditioning Error Codes

Alliance AC Maintenance Dubai

Alliance Air Conditioning Error Codes & Trouble Shooting.

1. Fixed speed Vertu midwall units

E1 – EEPROM error
E2 – Zero crossing detection error
E3 – Indoor fan error
E5 – Room temp sensor open or short
E6 – Indoor coil sensor open or short
EC – Refrigerant leak detected

2. Atlantic Midwall units

E1 – Outdoor tube sensor fault
E2 – Room temp sensor open or short
E3 – Indoor coil sensor open or short
E5 – Indoor fan fault
E6 – EEPROM error
E7 – External feedback fault – Check interconnecting wiring
E8 – Overheat detection / defrosting

3. Inverter midwall Ac units

E0 – EEPROM error
E1 – Indoor and outdoor communication error
E2 – Zero crossing detection error
E3 – Indoor fan error
E4 – Indoor room temp sensor open or short
E5 – Indoor coil sensor open or short
EC – Refrigerant leak detected
F1 – Outdoor temp sensor open or short
F2 – Condensor coil sensor open or short
F3 – Compressor discharge sensor open or short
F4 – Outdoor EEPROM error
P0 – IPM malfunction or IGBT over current
P1 – Over or under voltage protection
P2 – Temperature protection of compressor top (normally short of refrigerant)
P4 – Inverter compressor drive error

4. Fixed speed under ceiling/cassette/ducted Ac units

E1 – EEPROM error
E2 – Zero crossing detection error
E3 – Indoor fan error
E5 – Room temp sensor open or short
E6 – Indoor coil sensor open or short
EC – Refrigerant leak detected

5. Inverter under ceiling/cassette/ducted units

E0 – Communication between indoor and outdoor
E1 – Phase rotation/phase missing
E2 – Communication error between indoor unit and master unit
E4 – Outdoor temp sensor error
E5 – Compressor discharge temp sensor
E8 – Outdoor unit address error
E9 – Power volt error
H0 – Communication malfunction between IR341 and 780034
H1 – Communication between 0537 or 9177 and 780034
H2 – Quantity of outdoor unit decreases
H3 – Quantity of outdoor unit increases
H4 – P6 protection detected 3 times
H5 – P2 detected 3 times in 30 minutes
H6 – P4 detected 3 times in 100 minutes
H7 – Indoor unit decrease error
H8 – Discharge pressure sensor error
H9 – P9 detected 3 times in 30 minutes
P0 – Inverter compressor top temperature protection
P1 – HP protection
P2 – LP protection
P3 – Inverter compressor current protection
P4 – Compressor discharge temp protection (short of refrigerant)
P5 – Outdoor condensor high temp protection
P6 – Inverter module protection
P7 – Current protection No.1 Fixed compressor
P8 – Current protection No.2 Fixed compressor
P9 – Fan motor protection
L0 – DC inverter module protection
L1 – DC supply low voltage
L2 – DC supply high voltage protection
L4 – MEC Failure
L8 – Frequency protection
L9 – Frequency protection

6. MAC Cassette Ac units

E2 – Room temp sensor failure
E3 – Coil temp sensor failure
E4 – Condensor sensor failure
E5 – Water pump temp sensor
E6 – Outdoor malfunction
E7 – EEPROM malfunction
E8 – Water-level alarm

7. Package Ac units

E0 – Phase rotation/phase missing
E1 – Outdoor coil sensor in system A
E2 – Outdoor coil sensor in system B
E5 – Indoor coil sensor in system A
E6 – Indoor coil sensor in system B
E9 – Indoor temp sensor error
EA – Outdoor ambient sensor error
EB – Wire controller output error
P0 – Overcurrent protection in system A
P1 – Overcurrent protection in system B
P2 – Overcurrent protection for outdoor fan
P3 – Comprehensive protection for outdoor fan
P4 – Protection for HP/LP or discharge temp in system A
P5 – Protection for HP/LP or discharge temp in system B
P6 – HP protection initiated inT2 evaporator stops the outdoor unit fan
P7 – HP protection initiated inT2 evaporator stops the outdoor unit fan and compressor
P8 – Protection for condenser at high temp in system A
P9 – Protection for condenser at high temp in system B
PC – Anti-freezing protection for evaporator in system A
PD – Anti-freezing protection for evaporator in system B
PF – Defrosting

8. Portable Air conditioning units

HP -HP alarm
Ft – Full tray or full tank
Pf – Probe failure
Lt – Low temp
E1 – Room temp sensor
E2 – Evaporator temp sensor
E3 – Condensor temp sensor
P1 – Bottom tray is full

8. Water heaters (Retro fit)

E1 – Phase reversal/phase missing error
E2 – Communication error between unit and wired control or sensor damaged
E3 – Outlet water temp sensor error
E4 – Water temp sensor failure in the water tank
E5 – Condensor temp sensor error
E6 – Outdoor ambient temp sensor error
E7 – Sensor failure at water pump outlet
E9 – T8 temp sensor error
Ed – Sensor failure at double pipe refrigerant outlet
P1 – HP protection/air in system/pump not starting/no water
P2 – System current protection
P4 – Tt HP protection
P5 – Condenser HP protection
P8 – Protection for over temp at condenser outlet
P9 – Anti-freezing protection
Pb – Anti-freezing protection
HO – Indoor and outdoor units unmatched

Swimming pool heaters Error Codes

E1 – Phase rotation/phase missing
E2 – Outdoor unit and wire controller communication error
E3 – Outlet water temp sensor error
E4 – Inlet water temp sensor error
E5 – Evaporator pipe temp sensor error
E7 – Ambient temp sensor error
E9 – Water flow switch error
EE – Discharge pipe temp sensor error
P0 – Discharge pressure over-high protection
P1 – Low pressure protection
P4 – Compressor over current protection
P6 – Evaporator over temp protection
Pb – Anti-freeze protection
Pf – Discharge temp protection (too high)

Integrated water heater Error/Fault Codes

E0 – Error of sensor T5U
E1 – Error of sensor T5L
E2 – Tank and wired controller communication error
E4 – Condensor pipe temp sensor error
E5 – Outdoor ambient temp sensor error
E6 – Sensor Tp error
E8 – Electric leakage protection
LA – Ambient temp is outside of range 5° _ 43°
P0 – Condensor pipe temp overflow protection
P2 – High dicharge temp
P3 – Open compressor circuit protection
P4 – Compressor overcurrent protection
P8 – Open upper e-heater circuit protection
P9 – Upper e-heater overloaded protection
Pa – Open lower e-heater circuit protection
Pb – Lower e-heater overloaded protection

Commercial water heater Fault/Error Codes

E1 – Phase rotation/phase missing
E2 – Communication failure between wired remote and main unit
E3 – Outlet water temp sensor failure
E4 – Water temp sensor in the water tank failure
E5 – Condenser temp sensor failure
E6 – Outdoor ambient temp sensor failure
E7 – Electric heating pipe temp sensor failure
Ec – Water inlet temp sensor error
Eb – Exhaust temp sensor error (TP temp)
P0 – System LP protection
P1 – System HP protection (deficient circulating pump/pump faulty also possible)
P2 – Current protection for system 2
P3 – Current protection for system 1
P8 – Protection for excessive high outlet water temp
Pb – Anti-freezing protection

Contact us

 

Akai AC Error Codes and Troubleshooting

Akai AC Maintenance Dubai

Akai AC Error Codes and Troubleshooting in Dubai

Akai air conditioner is equipped with a self-diagnosis function to help you identify potential problems. Should you encounter problems with your air conditioner, contact our after sales support center using the details on the bottom of the page. However, before calling for Ac service, consult the self diagnosis information below.

Indicates “dF”or heating icon blinks: Blinks once per second: Defrost indication

Fan motor picture not running: Blinks once per second: Anti cold wind

E2: Blinks once every 8 seconds: Room temperature sensor fault

E3: Blinks twice every 8 seconds: Coil temperature sensor

E8: Blinks 3 times every 8 seconds: Indoor fan fault

E5: Blinks 6 times every 8 seconds: Outdoor feedback

E7: Blinks 7 times every 8 seconds: External feedback fault

E0: Blinks 3 times every 8 seconds: Open the door fault

E1: Blinks 4 times every 8 seconds: Outdoor tube temperature sensor faults

E6: Blinks 6 times every 8 seconds: (EEPROM) Communication failures

FF: Blinks once per second: Outdoor temperature exceeds scope (too cold)

Er: Indoor ambient temperature sensor failure

En: Evaporator pipe temprerature sensor failure

Eo: Condenser pipe temperature sensor failure

Ed: Evaporator de-frosting defect

Akai Ac Troubleshooting Guide

If you experience problems with your air conditioner, check for solutions in the table below. If the problem cannot be solved by simple adjustments, call the after sales support line, or contact a licensed air conditioner technician.

Problem: Air conditioner does not work.

Possible cause and solution:

  1. Power failure/disconnected/loose connections; check the power supply and ensure the unit is properly connected.
  2. Timer-on function is activated; cancel it.
  3. Damaged indoor/outdoor unit fan motor; call the after sales support line to arrange a service.
  4. Faulty compressor/thermomagnetic circuit breaker; call for service.
  5. Faulty protective device or fuse; call for service.
  6. Voltage is higher or lower than the required range; call for service.
  7. Electronic control board is damaged; call for service.

Problem: Remote control is unresponsive

Possible cause and solution:

  1. Remote control is too far away; move closer to the indoor unit
  2. Remote control batteries are flat; replace.
  3. Path to the signal receiver is blocked; remove obstructions

Problem: Cooling (Heating) efficiency is not good

Possible cause and solution:

  1. Unsuitable temperature setting — adjust fan speed.
  2. Blocked air intakes/ outlets — clear obstructions.
  3. Dirty air filter — clean the filter.
  4. Fan speed is set to LOW — increase.
  5. Other sources of heat in the room — check

Problem: Indoor unit does not work straight after restarting it

Possible cause and solution: This is not a fault. Once the air conditioner is stopped, you will have to wait for approximately 3 minutes before the unit can be restarted

Problem: Strange odour coming from the outlet

Possible cause and solution:

  1. Odour in the room (from building material, furniture or smoke) is recirculated
  2. Dirty air filter — clean the filter

Problem: Noise like running water when cooling

Possible cause and solution: Refrigerant is flowing inside the unit — no cause for concern

Problem: Mist is emitted when cooling

Possible cause and solution: Cold air used for rapid cooling of the air in the room may resemble fog — no cause for concern

Problem: Mist is emitted when heating

Possible cause and solution: Moisture from the defrosting process generates mist — no cause for concern.

Problem: Low noise is emitted during operation.

Possible cause and solution:

  1. A low hissing sound is caused by the refrigerant flowing.
  2. A low squeak sound is caused by the plastic parts expanding and contracting due to temperature fluctuations.

Problems with Wi-Fi connectivity

Problem: App does not show the air conditioner.

Possible cause and solution:

  1. Check and ensure you have Wi-Fi enabled on your smartphone.
  2. Check and ensure your smartphone and the air conditioner are connected to the same wireless router.
  3. If the air conditioner is correctly connected to the wireless router, the Wi-Fi indicator light on the display should be on

Problem: Remote control via smartphone does not work, despite correct connection

Possible cause and solution: Restart your AKAI Home App or reconnect your smartphone with the wireless router.

Contact us

Akai Portable AC Error Codes and Troubleshooting

Akai Portable Ac Maintenance Dubai

Akai Portable AC Error Codes and Troubleshooting

Before asking for repair or changing unit, please check:

Problems: The unit does not work

Causes: Power supply fault:

  1. Not plug in;
  2. Bad plug or socket;
  3. Fuse broken or wire broken;

Suggest Solutions:

  1. Plug in correctly;
  2. Change the plug or the socket;
  3. Send the unit to service center to change the fuse ;( fuse: 3.15A 250V )

Problems: The unit stop running automatically

Causes: Timer is set or room temperature is lower than set temperature;

Suggest Solutions: Close the TIMER or wait for it to run automatically;

Problems: In cooling mode, no cool air coming out;

Causes: Room temperature is lower than set temperature;

Suggest Solutions: Make the setting temperature lower than the room temperature; if it still does not work, call the local technician for repairing

Problems: Error code “E1” in LED window

Causes: Environment temperature sensor is broken.

Suggest Solutions: Replace the temperature sensor

Problems: Error code “E2” in LED window

Causes: Temperature sensor on the evaporator is broken

Suggest Solutions: Replace the sensor

Problems: Error code “E3” in LED window

Causes: Cooling system malfunction caused by the lack of refrigerant

Suggest Solutions: Contact the local repairing technician directly

Problems: Error code “E4” in LED window the red FULL light is bright

Causes: Water tray is full in the heating mode, but the unit is still working

Suggest Solutions: Empty water in water plate

Safety Cautions

  1. Do not use unit near gas appliance, fires or in the vicinity of flammable liquids.
  2. Do not let children put their fingers into the air outlet to avoid danger.
  3. Do not incline the unit more than 35° while moving the unit.
  4. Do not beat or extrude unit to prevent unit broken, do not vibrate the unit.
  5. Keep the unit two meters away from TV sets or radios to avoid the risk of electromagnetic interface.
  6. Do not use unit with the air outlet too close to walls or cover the outlet to avoid overheating.
  7. Do not use the unit in a very crowded room.
  8. Do not use the unit directly under sunshine to avoid surface color fading.
  9. Do not use the unit in water or near water to avoid leakage of electricity.
  10. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or similar qualified person in order to avoid a hazard.
  11. when the room temperature is higher than 25 degrees, it is better not to use the heating function.

Special Guide Line

  1. Do not incline the unit more than 5° degree, if so, please turn off power supply immediately and ask for advice from your local dealer.
  2. Do not spray insecticide or other chemicals to avoid deformation of plastic case.
  3. The unit, due to its moving feature, it can be moved from room to room and it is different from window type or split type air conditioner. If the unit cannot cool down the room temperature efficiently, it is not the unit’s quality problem. The unit can only work efficiently in certain room area. ( see technical specification )
  4. In order to prolong the unit’s lifetime, please empty the water completely in the water tray at the bottom of the unit while the unit is not going to use for a long period of time.
  5. The unit can drain water automatically. It is not necessary to use the hose to drain the water under the cooling mode because the condenser can evaporate the water.
  6. when turning “on” or “off” the unit under the heating mode, some noise of airflow inside the unit can be heard obviously, this is not a faulty problem, no need to repair.

Contact us